產(chǎn)品詳情
HGX22e/125-4S HG22P/125-4S天行健直銷原廠德國GEA BOCK船用壓縮機(jī)中國區(qū)總代理
福州天行健17年專業(yè)提供原廠德國Bizter、德國GEA Bock船用壓縮機(jī)及壓縮機(jī)零部件
Semi-hermetic suction gas-cooled reciprocating compressor in compact design. The best possible serviceability is provided by means of a replaceable drive motor, among other things. The compressor stands out due to its outstanding running comfort and efficient operating perbance. The suction shut-off valve can be rotated by 90° in each instance. Dependable mechanism lubrication is guaranteed by means of an oil pump which is independent of rotating direction, as well as a large-volume oil sump. An electronic motor protection uses PTC sensors in series to monitor the winding temperature and, if desired, the discharge gas temperature.
Colour: blue (RAL 5000)
Technical data
HGX22e/125-4 SApplication | Refrigeration & AC |
Compressor refrigeration capacity | 8.86 kW |
Power consumption | 3.20 kW |
Current draw (400 V) | 5.69 A |
Mass flow | 0.083 kg/s |
at following operating condition:
Refrigerant | R404A, R507 |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 2 / 45 mm / 40 mm |
Displacement 50/60 Hz (1450/1740 1/min) | 11,10 / 13,30 m3/h |
Voltage 1) | 220-240V Δ / 380-420V Y -3- 50Hz |
265-290V Δ / 440-480V Y -3- 60Hz | |
Max. working current 2) | 10.8 / 6.2 A |
Max. power consumption 2) | 3.6 kW |
Starting current (rotor blocked) 2) | 69.0 / 40.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 73 kg |
Frequency range 3) | 30 -70 Hz |
Max. permissible overpressure (g) (LP/HP) 4) | 19 / 28 bar |
Connection suction line SV | 22 mm - 7/8 " |
Connection discharge line DV | 16 mm - 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | BOCKlub E55 |
Oil type R22 | BOCKlub A46 |
Oil charge | 1,1 Ltr. |
Dimensions Length / Width / Height | 468 / 240 / 315 mm |
Sound power level LWA 5) | 68 db(A) @ -35/+40 °C |
67 db(A) @ -10/+45 °C | |
66 db(A) @ +5/+50 °C | |
Sound pressure level LpA 5) | 56 db(A) @ -35/+40 °C |
55 db(A) @ -10/+45 °C | |
54 db(A) @ +5/+50 °C |
Scope of supply
Semi-hermetic two cylinder reciprocating compressor with drive motor
Single-section compressor housing with hermetically integrated electric motor
Winding protection with PTC resistor sensors and electronic trigger unit INT69 G
115-230 V AC, 50/60 Hz, IP00
Oil pump
Possibility for connection of oil pressure safety switch MP55
Possibility of connection of oil level controllers ESK, Traxoil, AC+R or CARLY 6)
Oil charge:
HG: BOCKlub A46
HGX: BOCKlub E55
Sight glass
Suction and discharge line valve
Inert gas charge
Accessories
Oil sump heater
110-240 V - 1 - 50/60 Hz, 50-120 W, IP66
PTC heater self-regulating
USB converter for INT69 G Diagnose 7)
Thermal protection thermostat per cylinder cover 8)
Oil pressure safety switch MP55 230 V - 1 - 50/60 Hz, IP20 7)
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including adapter cable 7)
Modbus-LAN Gateway 230 V AC, 50/60 Hz, IP00 7)
Additional fan
230 V AC - 1 - 50 Hz, 97 W, IP44
230 V AC - 1 - 60 Hz, 128 W 7)
4 anti-vibration pads enclosed
Special voltage and/or frequency (on request)
Notes
1) |
Tolerance (± 10%) relates to the mean value of the voltage range. Other voltages and current types on request All data are based on voltage rms values |
2) |
- The stated value for the max. power consumption is valid for the adjusted power supply. - Starting current (rotor blocked):
|
3) | The maximum permissible working current of the compressor (Imax) must not be exceeded. Take account of the guidelines for use of frequency inverter (see compressor assembly instruction or selection software). |
4) |
LP = Low pressure HP = High pressure |
5) |
Declared dual-number noise emission values are in accordance with ISO 4871. The corresponding uncertainty to the sound power level is KWA = 2,5 dB and to the sound pressure level is KpA = 2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the standard rating points according to EN 12900.
|
6) | Only with additional adapter possible |
7) | Enclosure |
8) | Mounted |